Manufacturer | Siignals Limited |
---|---|
Specification Number | TOPAS 2540A |
Specification Status | Live |
Product Ref | SVACA01 |
Registration Date | 14/11/2024 |
Certificate Number | 2024-0274 |
Additional Documentation |
Product Details:
Registration to Appendices B, D and E only
Exceptions/exclusions
2.5 – the more rigorous CAT 1 Fault used as default in this scenario
2.6 – the more rigorous CAT 1 Fault used as default in this scenario
2.14 System reacts as per CAT 1 fail
2.37 -The final stage shall not display green but move through a 3-second amber to red. The controller will then begin to sequence as prescribed dependent upon operational mode once the signals have been at all-red for at least the maximum pre-set all-red period.
2.40 & 2.41 – Optional fault recording not provided
2.53 – optional item (vii) not provided
2.55, 2.56 & 2.57 – Optional phases and stages features not provided
E2.13 – System meets the requirement of E2.8